Permit Number: C13-1177
Permit Type: Commercial Building Permit - None BldgCombo
Address: 2801 DEBARR RD Anchorage
Location:
Work Description:

Interior build-out of 7th floor med/surg beds, 3rd floor finish upgrades, 1250 sq ft 2nd floor electrical room add'n, 1250 sq ft parking level generator room add'n, central plant upgrades / tb

2/13/15 paid for 50 inspections; 4/10/15 paid for 33 inspections; 7/17/15 paid for 24 inspections; 9/30/15 paid for 4 inspections

Status: Closed
Project Name: ALASKA REGIONAL RENOVATIONS & ELECTRICAL ADDITIONS
Review Type: Fire
Result: Correction
Result Date: 4/16/2013 8:41:28 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1st review 4/16/2013 - Corrections Required - See Comment 1.  OK to issue permit.  Mechanical block on fire folder not signed off by fire until oxygen system approved.  No other mechanical issues.

.

 Note: Per phone conversation & e-mail with Architect (Matt) - Daytank capacity is 450 gallons.  Landscaping will not interfer with hydrant access.  Oxygen tank will be deferred submital.

.

1.  Provide information on oxygen storage tank.  Include security fencing, bollard protection, tank design, signage, etc.  May be a deferred submital.