Tenant improvement to include mezzaine-gjs
Reassigned to Tony B.
PERMIT STILL ACTIVE PENDING APPROVAL OF X13-1249 PER G. STULLER - RED 8/29/2019
2/21/2013 Reviewed Plumbing & Mechanical - OK to issue P & M Permit. Waiting on deferred Electrical from Eric Cowling. Everything approved but electrical. Called Roger W. to discuss. He confirmed Eric will submit.
.
1. Need tio add a directional exit sign to get from the main entranc area to the rear 2nd exit.
2. RTU over 2000 cfm requires a smoke detector. If smoke detector is within unit on roof verify it will operate in expected cold temp and or provide heater or locate within building in duct.
3. Provide a device to indicate visual & audible trouble signal for detector per IFC 907.4.1. Show location on plans as location shall be approved.