Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C13-1074
Permit Type: Commercial Building Permit - None BldgCombo
Address: E 530 BENSON BLVD Anchorage
Location:
Work Description:

Tenant improvement to include mezzaine-gjs

Reassigned to Tony B.

PERMIT STILL ACTIVE PENDING APPROVAL OF X13-1249 PER G. STULLER - RED 8/29/2019

Status: Closed
Project Name: TREK BIKE SHOP
Review Type: Structural
Result: Correction
Result Date: 2/3/2013 11:16:44 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT INFORMATION

Permit Number: C13-1074

Project Name: Trek Bike Shop

Permit Manager: Tony Barganier | ph: (907) 343-8339 | barganierta@muni.org

 

Plan Review: Mark Panilo | ph: (907) 343-8081  fax: (907) 249-7679 | panilomm@muni.org

 

Please submit all information through your Permit Manager.

 

REVIEW STATUS

02/03/2013 – Initial review (308980).  Comments issued.

 

GENERAL

This review is code compliance review based on the requirements of the International Existing Building Code (IEBC), 2009 Edition, and all adopted references thereto, as amended by the Municipality of Anchorage in Anchorage Municipal Code (AMC) Title 23.  This review does not permit the violation of the building codes, nor any federal, state, or municipal regulation.

 

The following comments must be addressed before a permit may be issued.  Additional comments may be issued following review of submitted information.

 

1. TOP OF WALL DETAIL
Refer to Sheet 1.  Please provide details for the walls supporting the display screens, including top of wall conditions.

Reference:  IBC Section 1603.1

 

2. STATEMENT OF SPECIAL INSPECTIONS

Please provide a detailed statement of special inspections in accordance with IBC Chapter 17. This may be provided on the plans or as a separate document.

Reference: IBC Section 1705.2

 

3. SPECIAL INSPECTION PERSONNEL

Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.

Reference: AMC 23.15.1704.1.4

 

4. STAIR CONSTRUCTION

Refer to Sheet 2. Please provide details for the construction of the stairs to the mezzanine, including stringer sizes, tread sizes, and connections.

Reference:  IBC Section 1603.1

 

5. CHORD CONTINUITY

Refer to Sheet 2.  Please clarify the continuity of the diaphragm chords along Grids A and B.  It is not clear if the joists are continuous through Grid 2.

Reference: IBC Section 1604.4; ASCE 7 Section 12.10.1.1; NDS SDPWS Section 4.2.6.1

 

6. LATERAL SUPPORT OF DIAPHRAGM

Refer to Sheet 2.  Please clarify the lateral support of the diaphragm at Grid 3.  The diaphragm exceeds the limitations of open-front (3-sided) diaphragms, in both diaphragm length and aspect ratio.

Reference: NDS SDPWS Section 4.2.5.1.1

 

7. DIAPHRAGM NAILING

Refer to Sheet 2.  Please clarify the nailing of the diaphragm to the supporting framing.
Reference: NDS SDPWS Section 4.2.6.3

 

8. LOADS TO EXISTING COLUMN/FOOTING

Refer to Sheet 2.  The plans call for the midline GLB to be connected to an existing 6x6 at Grid A/2.  It is not clear if the column is supporting other loads. Please clarify, and provide verification of the column and footing capacity for additional loads if necessary.

Reference: IEBC Section 1003.2; AMC 23.65.1003.2

 

9. DIAPHRAGM DEFLECTION COMPATIBILITY

Refer to Sheets 2, 4.  Please clarify the compatibility of the diaphragm to displace against the existing partition walls, especially between Grids 2 and 3, where the diaphragm is not restrained from displacing plan north, but will pound the wall plan south.

Reference: ASCE 7 Section 12.12.4

 

10. WALL ANCHORAGES

Refer to Sheet 4.  The shear wall table provides wall loads, but there is no information regarding the anchorage of the wall for sliding.

Reference: IBC Section 1604.8; NDS SDPWS Section 4.3.6.4

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS