Reviewed on 1/25/2013 and changed status to Approved.
.
2nd Review 1/25/2013 FE location as shown exceeds 75 travel distance. Discussed via phone with Angela and they will adjust and e-mail with attachment showing final locations after getting customer approval. OK to issue permit as Inspector will field verify at final.
Note: Commonpath of travel measurement as noted on plans is incorrect but falls within code allowance. No action required.
__________
1st Review 12/26/2012 - Corrections Required. Provide a written response to comments along with revised plans. Call Tom Furch (907) 267-4964 to discuss furchtp@muni.org)
1. Provide fire extinguishers (FE's) as required per IFC 906. Show size, type, & location on plans. Mount along the path of egress, near exits, visible and unobstructed.