PERMIT INFORMATION
Permit Number: C12-2319
Change Order Number: X12-1731
Project Name: Grizzlys Pizza and Wings
Permit Manager: Jinny Rose Day | ph: (907) 343-8338 | dayjr@muni.org
Plan Review: Mark Panilo | ph: (907) 343-8081 fax: (907) 249-7679 | panilomm@muni.org
Please submit all information through your Permit Manager.
REVIEW STATUS
01/11/2013 – Initial review (308354). Comments issued.
1. SPECIAL INSPECTION PERSONNEL
Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.
Reference: AMC 23.15.1704.1.4
2. LATERAL BRACING OF HOODS
Refer to Sheet S2. Please address the following:
a. The option to attach the hoods to the partition wall does not provide torsional stability for the hoods. Please clarify restraint.
b. The option to use unistrut bracing does not provide enough information for the connections to the hood system, connection to bracing structure, permitted angles of bracing, etc. Please provide.
Reference: IBC Section 1603.1, 1604.4, 1604.8
3. FREEZER ANCHORAGEPlease provide design analysis for the freezer construction including bracing and anchorages. The detail provided on Sheet S2 is not sufficient for determining the anchorage requirements, and does not address the panel-to-panel or panel-to-structure connections.