Permit Number: X12-1731
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: changes to plans:  deleting of doors, changing dishwasher, baggage belt turning.
Status: Closed
Project Name: Change Order of Bldg App C12-2319
Review Type: Structural
Result: Correction
Result Date: 1/11/2013 4:14:33 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT INFORMATION

Permit Number: C12-2319

Change Order Number: X12-1731

Project Name: Grizzlys Pizza and Wings

Permit Manager: Jinny Rose Day | ph: (907) 343-8338 | dayjr@muni.org

 

Plan Review: Mark Panilo | ph: (907) 343-8081  fax: (907) 249-7679 | panilomm@muni.org

 

Please submit all information through your Permit Manager.

 

REVIEW STATUS

01/11/2013 – Initial review (308354).  Comments issued.

 

1. SPECIAL INSPECTION PERSONNEL

Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.

Reference: AMC 23.15.1704.1.4

 

2. LATERAL BRACING OF HOODS

Refer to Sheet S2.  Please address the following:

a. The option to attach the hoods to the partition wall does not provide torsional stability for the hoods.  Please clarify restraint.

b. The option to use unistrut bracing does not provide enough information for the connections to the hood system, connection to bracing structure, permitted angles of bracing, etc.  Please provide.

Reference: IBC Section 1603.1, 1604.4, 1604.8

 

3. FREEZER ANCHORAGE
Please provide design analysis for the freezer construction including bracing and anchorages.  The detail provided on Sheet S2 is not sufficient for determining the anchorage requirements, and does not address the panel-to-panel or panel-to-structure connections.

Reference: IBC Section 1603.1, 1604.4, 1604.8

 