Reviewed by: Bolen, Wayne A. Permit #: C12-1227
Phone: 343-8072 Date: 1/18/2013
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Jinny Day
Phone: 343-8338
Email: DayJR@muni.org
Project: UAA Stairs #2 and #3
Review Number: 308281
____________________________________________________________________________________
PERMIT STATUS (no response required) 1/18/2013: Review completed. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. Reference sheets 5, and 10 of the stair drawings and the original structural drawings. Please verify that the brace does not pass through the platform or where it does that this does not interfere with the expected behavior of the brace. By the elevation provided it appears the platform could prohibit the brace from buckling as it is expected to which could affect the performance of the system.