TENANT IMPROVEMENT (JINNY ROSE DAY)
CORE AND SHELL PERMIT C12-1269
Reviewed by: Bergstrom, Leigh W. Permit #: C12-3048
Phone: 343-8326 Date: 12/21/2012
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Jinny Day
Phone: 343-8338
Email: DayJR@muni.org
Project: Great Alaska Pizza Company
Review Number: 307916
1) STATUS: 12-19-12 Comments to be addressed. 12-21-12 APPROVED.
2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. RESOLVED 12-21-12.
3) M1 FS-1 is calling for a 3/4" grate. Is that 3/4" openings in the grate or was it supposed to be a 3/4 grate as opposed to a full or half grate? The M2 floor plans are depicting a 1/2 grate installation. Please clarify. RESOLVED PER RESUBMITTAL RECEIVED 12-20-12.
4) 1/M2 & 2/M2 These plans are refering to kitchen equipment numbers 8 and 53. According to the kitchen equipment schedule, item #8 was not used and there was no #53. Please clarify. RESOLVED PER RESUBMITTAL RECEIVED 12-20-12.
5) The 3-compartment sink requires an adjacent floor drain or flush mounted floor sink within 5 feet (UPC 704.3 plus local amendment). Please clarify. RESOLVED PER RESUBMITTAL RECEIVED 12-20-12.
6) M2 Cleanouts are required at hand sinks #17 and #17A. (UPC 707.4 Exception #1) RESOLVED PER RESUBMITTAL RECEIVED 12-20-12.
7) M2 Cast iron waste piping materials are not compatible with the byproducts being disposed of at the floor sink #FS-1 serving the soda dispenser. Please address. RESOLVED PER RESUBMITTAL RECEIVED 12-20-12.
8) 2/M2 It appears that there is a 1/2" HW line connecting to the ice machine. Please clarify. RESOLVED PER RESUBMITTAL RECEIVED 12-20-12.
9) 2/M2 The domestic water service to the ice maker w/ bin and water filter requires back flow protection. (UPC 603) RESOLVED PER RESUBMITTAL RECEIVED 12-20-12.
10) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RESOLVED 12-21-12.