Project: 2925 Debarr Road
Review Number: 307769
Permit Status: Corrections/ approved 1/8/2013
1) Provide a cut sheet for the BPS units and total amperage load per circuit for verification of load capacity.
2) Note: I redlined the plans that show two additional strobes for compliance.
The items above are resolved as of 1/8/2013