12/29/2012 Corrections Required. Provide written response to comments (May e-mail to furchtp@muni.org) minor changes may be included on 8.5 x 11 supplemental sheet and added to conformed drawings upon final update. Call tom furch @ (907) 267-4964 to discuss or confirm. Note: Bollard detail on sheet A9 does not meet requirements of IFC 312 and should not be used where vehicle impact protection required by the fire code is specifiied. Fire Protection drawings included in the submital were reviewed for info only. Any changes to fire protection systems shall be submitted as a change to the appropriate permit/plans.
.
1. General note #6 on sheet SWA1 referencing fire extinguisher (FE) locations is not acceptable and locations shall be detailed on the drawing to eliminate conflicts at final inspection. Show locations on plans.
2. The dining area requires two exits but is missing the exit sign from the exit back into the main store. Please comment and add as required. See sheet SWE1.