Permit Number: X12-2074
Permit Type: Commercial Building Permit - ChangeOrdr BldgNew
Address: N 1074 MULDOON RD Anchorage
Location:
Work Description: Addendum #2 & CCD#1 / tb
Status: Closed
Project Name: Change Order of Bldg App C12-1324
Review Type: Fire
Result: Correction
Result Date: 12/28/2012 11:45:21 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

12/29/2012 Corrections Required. Provide written response to comments (May e-mail to furchtp@muni.org) minor changes may be included on 8.5 x 11 supplemental sheet and added to conformed drawings upon final update.  Call tom furch @ (907) 267-4964 to discuss or confirm.  Note:  Bollard detail on sheet A9 does not meet requirements of IFC 312 and should not be used where vehicle impact protection required by the fire code is specifiied.  Fire Protection drawings included in the submital were reviewed for info only.  Any changes to fire protection systems shall be submitted as a change to the appropriate permit/plans.

.

1.  General note #6 on sheet SWA1 referencing fire extinguisher (FE) locations is not acceptable and locations shall be detailed on the drawing to eliminate conflicts at final inspection.  Show locations on plans.

.

2.  The dining area requires two exits but is missing the exit sign from the exit back into the main store.  Please comment and add as required.  See sheet SWE1.