Reviewed by: Crafts, Donald E. Permit #: C12-1324; X12-2074
Phone: 343-8451 Date: 12/26/2012
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierT@muni.org
Project: SAM'S CLUB 6602 - 1074 N MULDOON RD
Review Number: 307678
1. Status: Architectural Corrections required for this Change Order. 12/26/12
2. The following comments based on the 2009 International Building Code (IBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Please provide assurance that the Building Envelope meets or exceeds the Energy Efficiency requirements of IBC Section 1301.1 and The International Energy Conservation Code (IECC) Chapter 5 and Local Amendments to IECC Chapter 5 requirements. Show compliance with the requirements of Climate Zone 7 in IECC Table 502.2(1) and 502.2(3) as well as the Local Amendment to IECC Table 502.2(1) on unheated slabs. Note that the Metal Stud Framing with R-19 insulation between the studs produces an R value that is approximately 8. Is there a roof assembly indicated in the plans? The door schedule indicates hollow metal for exterior doors. Are these intended to be insulated hollow metal for exterior doors? Has there been an energy analysis submitted for review? 12/26/12