Reviewed by: Bolen, Wayne A. Permit #: C12-1324
Phone: 343-8072 Date: 1/10/2013
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Sam’s Club Wheelchair Lift
Review Number: 307673
____________________________________________________________________________________
PERMIT STATUS
1/10/2013 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. There has been no structural details or design provided for the wheel chair lift. Please provide the following:
A. Tie back detail that is designed for the 177 lb F5 reaction.
B. Check of the slab to support F3 or F4 whichever would control the design (F3 is the higher reaction, but it is not clear which causes the biggest effect).