2nd Review 11/29/2012 @ counter for new sheet A3 revision 5. Corrections still required. No response to initial comments were provided. Comment numbers refer to original comments that have not been resolved.
.
3. The fire extinguisher (FE) that has been relocated to the breakroom is both obscured and not along the path of egress. It's relocation causes travel distance from the FE to the file room to exceed 75ft. Add additional FE's or adjust to meet maximum allowable travel distance. Note: It is understood that the wall in breakroom 211 housing the FEC has not been constructed in the area as shown. the exact location should be shown.
4. Since the new door by the file room serves exiting in both directions and the space requires two exits, exit signs are required on both sides of the door. Please add to plans.
5. Original comment concerning adjustments to the sprinkler and fire alarm system has not been addressed. Since you are creating a corridor it is expected that additional fire alarm devices will be required in this corridor within 15ft of each end. Include these devices in the re-submital.