Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X12-2006
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address:
Location:
Work Description: Additional wall installation / tb
Status: Closed
Project Name: Change Order of Bldg App C12-2771
Review Type: Architectural
Result: Correction
Result Date: 11/21/2012 12:09:28 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C12-2771; X12-2006

Phone: 343-8451                                                                        Date: 11/21/2012

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierT@muni.org

Project: ALASKA USA 2ND FLOOR - B STREET NORTH BLDG.

Review Number: 307016

 

1.  Status: Architectural Corrections required.  11/21/12

 

2.  The following comments (for this change order only) based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Limited scope; another portion of the 2nd floor buildout; the rest of this floor buildout will be submitted at a later date.  11/21/12

 

4.  Drawing A3, Floor Plan; Please Clarify the Means of Egress Illumination.  Verify/show the emergency exit discharge lighting per IBC Section 1006.3.  Most should be existing in the building; however, the new buildout requires additional emergency lighting in the newly created corridor. 11/21/12

 

5.  Drawing A3, Floor Plan; The plan does not indicate exit sign locations.  Verify/show the exit sign locations per IBC Section 1011.1.  Most should be existing in the building; however, the new buildout requires additional exit signs.  11/21/12

 

6.  Drawing A3, Floor Plan; Per IBC Section 906, Show size, type, & location of fire extinguishers, both existing & new.  Extinguishers shall be located along the path of egress, near the exits, a maximum 75 ft travel from any point within the building to the extinguisher.  The new

conference room door is located directly on then wall where a fire extinguisher was previously located on the base permit.  11/21/12

7.  Drawing Axxx, Floor Plan; No door Schedule is provided with the plans.  Additionally, the plans do not provide any door hardware details.  Please provide door hardware details on the plans or a new Door Schedule showing hardware type & rating of both new & existing doors that meet the requirements of IBC Section 1008.1.8 and 1008.1.9.  11/21/12

 

8.  Drawing A3, Floor Plan; The fire alarm system and sprinkler system are affected by this buildout.  See Fire comments for resolution of these issues 11/21/12

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS