Permit Type: Commercial Building Permit - None BldgAlter
Address: N 1142 MULDOON RD Anchorage
Location:
Work Description:

TENANT IMPROVEMENT (JINNY ROSE DAY)

DON'T ISSUE CCO/CO UNTIL CORE AND SHELL HAS ONE C12-1269

 

Status: Closed
Project Name: NAILS COUTURE
Review Type: Mechanical
Result: Correction
Result Date: 11/20/2012 4:00:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C12-2975

Phone: 343-8326                                                                            Date: 11/20/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: NAILS COUTURE

Review Number: 306918

 

1) STATUS:  11-20-12 Comments to be addressed.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 

3) 1/M2.0          IMC Table 403.3 Note "h" for nail salons, requires exhaust systems that capture the contaminants and odors at their source; the intent being that no one should be breathing them in. The floor plan is laid out such that the nail table operator would be between the source and the exhaust and exposed to the adverse elements all throughout their work day. If one end of the table were to be placed against the wall directly beneath the exhaust grille, the fumes and contaminants would be drawn across the table top directly into the exhaust system with little or no exposure to personnel.

 

4) 1/M2.0          Clarify the return air path from Esthetician 102 back to the rooftop unit.

 

5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.

  

 

 