Permit Number: X12-1900
Permit Type: Commercial Building Permit - ChangeOrdr BldgNew
Address: N 1074 MULDOON RD Anchorage
Location:
Work Description: DEFERRED SUB:  roof joists/calculations / tb
Status: Closed
Project Name: Change Order of Bldg App C12-1324
Review Type: Structural
Result: Approved
Result Date: 12/11/2012 11:01:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

  1. Has the engineer of record reviewed an approved the submittal. This is required per the Anchorage Administrative Code section 23.10.104.9.
  2. It doesn’t appear as if the joist plans were submitted. I tried printing to 11X17, and the text is just too small. Please provide two half size copies of the drawings (one for MOA and one for field).
  3. There are girder braces shown on the plans and a typical detail showing the installation of these braces, but no brace sizes are indicated. Please provide a schedule of the brace sizes. We do not need the length of the braces just the sizes.
  4. Please provide one addition copy of the joist elevations. We have one copy for MOA, but need another for the field. We do not need a copy of all of the calculations. Just the joist elevation sheets that indicate the chord and web member sizes.