Permit Number: C12-2411
Permit Type: Commercial Building Permit - None BldgAdd
Address: 4825 AIRCRAFT DR Anchorage
Location:
Work Description: Construction of new accessory storage & installation of new ceiling hoist & 220V outlets; work will include construction of a new floating dock & installation of new security fence/gates & CCTV cameras / tb
Status: Issued
Project Name: LAKE HOOD ALASKA STATE TROOPERS AIRCRAFT HANGAR
Review Type: Fire
Result: NA
Result Date: 9/18/2012 4:17:21 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1st Review 8/7/2012 - Corrections Required.  Provide written response to comments along with revised plans.

.

1.  The new electronic security gate obstructs the required fire access to the facility.  The gate is too narrow and requires a "Knox" brand keyed override.

.

2.  Provide a fire extinguisher (FE) on the mezzanine level near the stairs.  Show size, type, & location on plans.