Reviewed by: Crafts, Donald E. Permit #: C12-2411
Phone: 343-8451 Date: 8/27/2012
Fax: 249-7652
Email: CraftsDE@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierT@muni.org
Project: LAKE HOOD ALASKA STATE TROOPERS - Mezzanine & Floating Dock
Review Number: 298184
1. Status: Architectural Corrections required. 8/27/12
2. The following comments based on the 2009 International Building Code (IBC) and 2009 International Existing Building Code (IEBC) must be resolved before a permit is issued. The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.
3. Drawing No. T-1, Building Code Analysis, For the Building Description; Clarify the area of the Mezzanine located over the new Parts Storage Room. The Mezzanine area appears to be 1,130 SF. 8/27/12
4. Drawing No. T-1, Building Code Analysis, For the Building Occupancy; Revise: “S-2 Aircraft” To: “S-1 Aircraft” or clarify what will be stored in the new Parts Storage Room and the Mezzanine. 8/27/12
5. Drawing No. T-1, Building Code Analysis, For the Building Occupant Load; Revise: “Mezzanine = 3” To: “Mezzanine = 4” or clarify why 300 SF per occupant is not used. 8/27/12
6. Drawing No. T-1, Building Code Analysis, For the Building Occupant Load; Revise: “Storage = 3” To: “Storage = 4” or clarify why 300 SF per occupant is not used. 8/27/12
7. Drawing No. A-2, Ground Floor Plan and Door Types, Identify the door sizes on the plans and verify compliance with IBC Sec. 1008.1.1. Verify compliance with IBC Sec. 1008.1.8 for all egress doors. 8/27/12
8. Drawing No. A-2, Ground Floor Plan, Window Types, Wall Types, Door Types and Frame Types; Please cross-tie the the Types to the specific locations on the Plan. 8/27/12
9. Drawing No. A-3, 2ND Floor Plan; Verify/show fire extinguisher locations per IBC Section 906.1. Most should be existing; however, the new Mezzanine requires at least one fire extinguisher near the new exit. Show fire extinguisher size, type, & location on plans. 8/27/12