TENANT IMPROVEMENT (JINNY ROSE DAY) CORE AND SHELL PERMIT C11-2350
2nd Review 10/4/2012 - Corrections Required. Provide a written response to comments along with revised plans.
.
1. Clarify the note for Door 329 - "Door to be lockable". Locking this door against egress could create an exiting issue. Although you could argue that this is not a required exit from the suite keep in mind that most occupants tend to exit thru the door they enter and that even if the argument was allowed you would have to reconfigure exit signage directing occupants to door 364. Is there a method to lock door 329 from room 301 but still have it useable from corridor 340? Locks on the type of door you are specifying typically do not allow the door to operate from either direction. Please comment.