PERMIT INFORMATION
Permit Number: C12-1957
Change Order Number: X12-1678
Project Name: Horizon Lines
Permit Manager: Tony Barganier | ph: (907) 343-8339 | barganierta@muni.org
Plan Review: Mark Panilo | ph: (907) 343-8081 fax: (907) 249-7679 | panilomm@muni.org
Please submit all information through your Permit Manager.
REVIEW STATUS
09/20/2012 – Initial review (301630). Comments issued.
1. BRIDGE CRANE PLANS
Please provide plans showing the construction of the bridge rails and columns.
Reference: IBC Section 1603.1
2. STATEMENT OF SPECIAL INSPECTIONS
Please provide a detailed statement of special inspections in accordance with IBC Chapter 17. This may be provided on the plans or as a separate document.
Reference: IBC Section 1705.2
3. SPECIAL INSPECTION PERSONNEL
Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.
Reference: AMC 23.15.1704.1.4