Permit Number: M12-1566
Permit Type: Commercial Trade Permit - Alteration Mechanical
Address: 4111 AVIATION AVE Anchorage
Location:
Work Description: REPLACE TWO EXISTING BOILERS W/ THREE NEW BOILERS (JINNY ROSE DAY)
Status: Closed
Project Name: SOA DOT OFFICE
Review Type: Mechanical
Result: Approved
Result Date: 8/20/2012 10:47:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Reviewed by: Bergstrom, Leigh W.                                               Permit #: M12-1566

Phone: 343-8326                                                                            Date: 8/20/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: DOT & PF Aviation Building

Review Number: 300719

 

1) STATUS:  8-09-12 Comments to be addressed.     8-20-12 APPROVED.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.  RESOLVED 8-20-12. 

 

3) Provide structural & seismic calculations plus fastening details for B-1, 2 & 3 to include engineers stamp and signature, for structural review on a deferred submittal basis.             RESOLVED PER RESUBMITTAL RECEIVED 8-15-12.          

 

4) Clarify the size and location of the required boiler system expansion tank. (IMC 1009.1)                        RESOLVED PER RESUBMITTAL RECEIVED 8-15-12.          

 

5) M5.0        Condensate from the boilers is required to be processed through a condensate neutralizer (IMC 307.2 plus local amendment).       RESOLVED PER RESUBMITTAL RECEIVED 8-15-12.          

 

6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.              RESOLVED 8-20-12.          

 