Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C12-2435
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: TENANT IMPROVEMENT: SUITE C2249 INCLUDES ELEC, PLMB, MECH AND FIRE SYSTEMS (JINNY ROSE DAY)
Status: Closed
Project Name: SILVER GULCH BREWING & BOTTLING COMPANY
Review Type: Plumbing
Result: Approved
Result Date: 8/7/2012 1:25:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C12-2435

Phone: 343-8326                                                                            Date: 8/7/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: Silver Gulch Brewing

Review Number: 299997

 

1) STATUS:   7-30-12 Comments to be addressed.  Status: Full Plumbing Approval by DECrafts.  8/7/12

 

2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.

 

3) M4.0            The 3/4" gas supply to Brick Oven "O-1" (240 MBH @ 110' appears to be undersized per UPC Table 12-8.   Resolved.  Revised to 1" with a reducer at the equipment connection.  8/7/12

 

4) Provide specifications for allowable pipe and fittings for the various plumbing systems keeping in mind that any material above the ceiling on either level will need to be plenum rated if the ceiling area is being used as a return air plenum (IMC 602.2.1).   Resolved.  Table of items in the ceiling area is now provided.  8/7/12

 

5) The 3-compartment sink requires a center waste outlet (UPC 1001.2) with vented P-trap (1014.1.1) and a vented flow control fitting (UPC 1014.2.1). Please clarify.   Resolved.  8/7/12

 

6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.

 

 

 

 

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS