Reviewed by: Bergstrom, Leigh W. Permit #: C12-2319
Phone: 343-8326 Date: 7/26/2012
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Jinny Day
Phone: 343-8338
Email: DayJR@muni.org
Project: Grizzlys Pizza and Wings
Review Number: 298324
1) STATUS: 7-16-12 Comments to be addressed. Status: Full Mechanical Approval by Donald Crafts. 7/26/12
2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.
3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for Evaporators K-20A & 21A, Type I Kitchen Hoods K-22 & 22A, MAU-1 (K-24) and Dishwasher Hood K-43 to include engineers stamp and signature, for structural review on a deferred submittal basis. Resolved. 7/26/12
4) M2 EF-1, 2 & 3 provide a total of 8980 CFM of exhaust and MAU-1 provides 3000 CFM of makeup air leaving a diffference of 5980 CFM. Please clarify the balance of airflow required per IMC 501.3. Resolved. 7/26/12
5) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.