Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C12-2365
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2925 DEBARR RD Anchorage
Location:
Work Description:

TENANT IMPROVEMENT (JINNY ROSE DAY)  CORE AND SHELL PERMIT C11-2350

Status: Closed
Project Name: ALASKA ONCOLOGY & HEMATOLOGY
Review Type: Architectural
Result: Correction
Result Date: 8/1/2012 10:58:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C12-2365

Phone: 343-8326                                                                            Date: 8/01/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: Alaska Oncology & Hematology

Review Number: 297313

 

1) STATUS:   8-01-12 Comments to be addressed.

 

2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.

 

3) T0.3            Wall Types "A", "B", "D" & "E" require top of wall slip joints per IBC 1604.3.1.

 

4) A2.1            Clarify the use for the rooms entitled "Bed" #353 & #354.

 

5) A2.1            There are two sections taken, one in Infusion Center #356 and one in Bay #7, that reference X/A8.X. Please clarify.

 

6) A2.2            Door Type 7 has a reference in parenthesis of (Pharmacy). This door type is not located at Pharmacy #361A. Please clarify.

 

7) A2.2            Door frame types "B" & "F" with interior relites require safety glazing (IBC 2406.4.6).

 

8) A2.2            Provide door hardware specifications that were not included in the submittal package.

 

9) 1/A2.4         The required ADA water closet clear space is 60" minimum, measured perpendicular from the side wall (604.3.1). The lavatory location is not in compliance.

 

10) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.

 

 