Reviewed by: Bergstrom, Leigh W. Permit #: C12-1227
Phone: 343-8326 Date: 6/29/2012
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Jinny Day
Phone: 343-8338
Email: DayJR@muni.org
Project: UAA SPORTS ARENA
Review Number: 295114
1) STATUS: 4-20-12 Comments to be addressed. 5-25-12 COMMENTS TO BE ADDRESSED. 6-29-12 UNDERGROUND PLUMBING ONLY, APPROVED. PROVIDE 100% DRAWINGS SO THAT A COMPLETE REVIEW CAN BE ACCOMPLISHED. COMMENTS TO BE ADDRESSED.
2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. RESOLVED 6-29-12.
3) M101 FD-2 at column line "D.7" and "10.3" appears to require trap seal protection. (UPC 1007). Please clarify. RESOLVED PER RESUBMITTAL RECEIVED 6-14-12.
4) M101 The 2" FCO upstream of fixture K-1 serves a 3" W line 8 feet downstream. This FCO and interconnecting piping are required to be at least the same size as the 3" main downstream. (UPC Table 7-6) RESOLVED PER RESUBMITTAL RECEIVED 5-14-12.
5) M101 The 2" FCO adjacent to fixture K-4 serves a 3" W main downstream and a 4" main further downstream. This cleanout is required to be the same size as the largest pipe served. (UPC Table 7-6) 5-25-12 UNRESOLVED. THIS ITEM WAS NOT ADDRESSED. RESOLVED PER RESUBMITTAL RECEIVED 6-14-12.
6) M102 FD-1 in Laundry B1220 requires trap seal protection (UPC 1007). 5-25-12 UNRESOLVED. THIS ITEM WAS NOT ADDRESSED. RESOLVED PER RESUBMITTAL RECEIVED 6-14-12.
7) M102 The floor drains (FD-1) in Toilet B1244, Toilet B1248 and Locker B1247 require trap seal protection. (UPC 1007) RESOLVED PER RESUBMITTAL RECEIVED 6-14-12.
8) M102 Five floor drains were deleted from Showers B1257, B1262. B1267, B1272 and B1277 with revision #1; however, the plans still indicate a sloped floor to accumulate water. Please clarify. RESOLVED PER RESUBMITTAL RECEIVED 6-14-12.
9) M104 The four FD-1's at the 4 exits from the Performance Gymnasium, one in Janitor B1130 and one in Toilet B1210 require trap seal protection (UPC 1007). 5-25-12 UNRESOLVED. THIS ITEM WAS NOT ADDRESSED. RESOLVED PER RESUBMITTAL RECEIVED 6-14-12.
10) M105 FD-1 adjacent to column lines "2" and "D" requires trap seal protection. (UPC 1007) RESOLVED PER RESUBMITTAL RECEIVED 6-14-12.
11) M106 Six floor drains were deleted from Showers B1052, B1057, B1062, B1067, B1072 and B1077 with revision #1; however, the plans still indicate a sloped floor to accumulate water. Please clarify. RESOLVED PER RESUBMITTAL RECEIVED 6-14-12.
12) M106 The floor drains in Ski Storage B1015 and Pump B1017 require trap seal protection. (UPC 1007). RESOLVED PER RESUBMITTAL RECEIVED 5-14-12.
13) M106 Two floor drains (FD-2) in Catering Kitchen 1033 require trap seal protection. (UPC 1007) RESOLVED PER RESUBMITTAL RECEIVED 6-14-12.
14) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.