Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C12-1269
Permit Type: Commercial Building Permit - None BldgNew
Address: N 1142 MULDOON RD Anchorage
Location:
Work Description:

CORE AND SHELL ONLY:  17,383 SQ FT (M) JINNY ROSE DAY)

 

NOTE:  FILL/GRADE MASTER # 07-5165

Status: Closed
Project Name: TIKAHTNU COMMONS MALL BLDG F
Review Type: Plumbing
Result: Approved
Result Date: 6/6/2012 11:53:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C12-1269

Phone: 343-8326                                                                            Date: 6/06/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: Tikahtnu Commons Mall Bldg F

Review Number: 294178

 

1) STATUS:   3-20-12 Comments to be addressed.         5-14-12 COMMENTS TO BE ADDRESSED.             6-6-12 APPROVED.

 

2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.        RESOLVED 5-14-12.

 

3) M2.0 Boiler Piping Diagram             The domestic cold water supply to the boiler is required to be protected from cross-contamination per UPC 603. Also, as shown it appears that the primary makeup heating fluid source will be the domestic water system. This could be problematic for a snow melt system.            RESOLVED PER RESUBMITTAL RECEIVED 5-1-12.

 

4) P100         One of the P-4 floor drain P-traps in the mechanical room is missing a plumbing vent. (UPC 901.1)           5-14-12 UNRESOLVED. THE ADDED VENT IS ACKNOWLEDGED; HOWEVER, A BOILER ROOM FLOOR DRAIN IS REQUIRED WHERE THE FLOOR SLOPES TO THE DRAIN (IMC 1004.6) AND AN AREA DRAIN IS REQUIRED AT THE RPBP (UPC 603.3.9 PLUS LOCAL AMENDMENT) WITH THE FLOOR SLOPING TO THE DRAIN.           RESOLVED PER RESUBMITTAL RECEIVED 5-31-12.

 

5) P100         One of the P-4 floor drain P-traps is depicted as being vented to atmosphere outside of the building perimeter. Please clarify.                 RESOLVED PER RESUBMITTAL RECEIVED 5-1-12.

 

6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.    RESOLVED 6-6-12.

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS