Permit Number: C12-1776
Permit Type: Commercial Building Permit - None BldgAlter
Address: S 5380 AIRCRAFT DR Anchorage
Location:
Work Description: Construct a bulk fuel facility with 2 20k gallon fuel tanks, a fuel truck loading and unloading area, and a truck parking area.-  gjs  Reassigned to Tony Barganier
Status: Closed
Project Name: FLEET FUELING STATION & PARKING
Review Type: Fire
Result: Approved
Result Date: 6/22/2012 11:47:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Approved 6/20/2012 - Per phone conversation with CRW Engineer addressed concerns - Tank is double wall protected -Dike area is not required but provided.  Height of tank support is < 8 inches - 2 hr protection not required.  reference to 2006 IFC on sheet G3 is typo error - Project meets 2009 code edition.  Addressing location of fuel shutoff with electrical engineer will locate further from area as required.

.

Per phone call from Engineer the shut off is within requirements of NFPA for bulk storage/process transfer.  (Not > 100ft away).  Since this is not a fleet fueling station for fueling motor vehicle fuel tanks the 20 to 100ft distance in IFC 22 does not apply.  Researched & accepted. 6/22/2012