Electrical Comments
Reviewed by: David Abuobaid Permit #: C12-1325
Phone: 343-8333 Date: 3/22/2012
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierWA@muni.org
Project: Sams/s Fuel Station (Fax: 214-749-0601)
____________________________________________________________________________________
5/8/2012
The comment below has been addressed and added to the plans. Approved
1. Please address the following comments for approval. 3/22/2012
2. The following comments based on the 2008 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications do not permit the violation of any section of the NEC or any federal, state or local regulations.
3. EQUIPMENT REQUIRES THIRD PARTY LISTING:Please be aware that all equipment will require and be checked for third party listing per NEC 110-3. Any new or existing equipment to be reused or relocated will be checked for listing by the electrical inspector. Any equipment found without a listing will be required to go through testing to gain approval. Inspector to field verify.
4. DOCUMENTATION (HAZARDOUS LOCATION CLASSIFIED):
Sheet FKE1 (Gas Pumps). Please add to the plans the floor plans for the canopy. Add hazardous classification diagram around the canopy and the gas dispensing units as required by NEC Sections 500.4 and 514.
5. When the above comments have been addressed, please update the electrical plans at the MOA
Plans Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical engineers stamp and signature.