Reviewed by: Bergstrom, Leigh W. Permit #: C12-1324
Phone: 343-8326 Date: 5/09/2012
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Sam's Club 6602
Review Number: 292861
1) STATUS: 4-2-12 Comments to be addressed. 5-09-12 APPROVED.
2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. RESOLVED 5-09-12.
3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for RTU-1 thru 24, AHU-1, EH-1& 2 and the Compressor House to include engineers stamp and signature, for structural review on a deferred submittal basis. RESOLVED 5-09-12.
4) M1, M2 & GM1 "Non-metallic ducts (fabric duct) shall be constructed with Class 0 or Class 1 duct material in accordance with UL 181." (IMC 603.5) Provide submittal literature supporting the requirements. RESOLVED PER RESUBMITTAL RECEIVED 5-08-12.
5) 3/M2 Clarify the makeup air path into the janitors closet. RESOLVED PER RESUBMITTAL RECEIVED 5-08-12.
6) GM1 The Fire Pump Room is a required 1-Hour enclosure (with sprinkler) and requires fire dampers on any duct penetrations or air transfer penetrations. (IMC 716.5.2) RESOLVED PER RESUBMITTAL RECEIVED 5-08-12.
7) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RESOLVED 5-09-12.