Permit Number: F12-1146
Permit Type: Commercial Trade Permit - Alteration Fire
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: FIRE ALARM DEVICES 8 (JINNY ROSE DAY)
Status: Closed
Project Name: KULIS BLDG 23, 37, 46
Review Type: Fire System
Result: Approved
Result Date: 5/9/2012 9:16:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Municipality of Anchorage

 

Building Safety Division

 

Fire systems Comments

 

Reviewed by: Mark Warren                                            Permit #: f12-1146

Phone: 267-4992                                                                        Date: 5/4/2012

Right Fax; 249-7397

Email: warrenmj@muni.org

Permit Manager: Jinny Day

Phone: 267-4992

Email: DayJR@muni.org

Project: Kulis buildings 23, 37, 45

Review Number: 291499

____________________________________________________________________________________

 

PERMIT STATUS; Approved 5/9/2012. The items below are tied to the alternate means and shall be satisfied at the final inspection prior approval

 

Page 3 of the alternate request contains the description of a sequence of events. It states that upon receipt of an alarm signal that within 10-30 seconds the Airport police and Fire are called; after 40-60 seconds the MOA fire department is called.

I would approve this method but not before the following comments are resolved.

1) Prove that the phone line connection is monitored for integrity to show up as a trouble signal and that there is redundancy in the system for a secondary line.

2) Provide information as to how AFD confirms the location of these buildings for efficient response time.

3) Provide an annual inspection report of the present alarm system of the buildings to confirm proper operation of the system at the time of the final inspection. 

 

 

 

Mark Warren, Systems Plan Review

Anchorage Fire Department, Fire Prevention Division