Permit Number: F12-1128
Permit Type: Commercial Trade Permit - Alteration Fire
Address: 3610 SHARON GAGNON LN Anchorage
Location:
Work Description: FIRE ALARM 190 DEVICES (JINNY ROSE DAY)
Status: Closed
Project Name: UAA MAC 6 HOUSING
Review Type: Fire System
Result: Approved
Result Date: 5/14/2012 1:56:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Municipality of Anchorage

 

Building Safety Division

 

Fire systems Comments

 

Reviewed by: Mark Warren                                            Permit #: f12-1128

Phone: 267-4992                                                                        Date: 5/7/2012 Approved 5/14/2012

 

Right Fax; 249-7397

Email: warrenmj@muni.org

Permit Manager: Jinny Day

Phone: 267-4992

Email: DayJR@muni.org

Project: MAC housing unit #6  

Review Number: 291631

____________________________________________________________________________________

 

PERMIT STATUS; Corrections. Approved 5/14/2012

1)      Provide detection on the room between units 112 and 113 on page 1.

2)      Install complete visibility notification on units 113 and 107.

3)      Install all smoke detection a minimum 26 inches away from bathrooms and 21 feet from cooking appliances.

 The above comments were rosolved with additional information. 5/14/2012.

 

 

 

Mark Warren, Systems Plan Review

Anchorage Fire Department, Fire Prevention Division