Permit Number: M12-1212
Permit Type: Commercial Trade Permit - Alteration Mechanical
Address: 2801 DEBARR RD Anchorage
Location:
Work Description: Adding new flat plate heat exchanger to existing boiler system to enable building system to run at a higher pressure than boiler (2) inspections - BWP

*** CONT CHANGED NAME ON 10/23/24 FROM SUPERIOR MECH TO THE SUPERIOR GROUP-  SLO

Status: Issued
Project Name: Alaska Regional Boiler Room
Review Type: Mechanical
Result: Correction
Result Date: 4/11/2012 10:16:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh                                                    Permit #: M12-1212

Phone: 343-8326                                                                            Date: 4/11/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker 

Phone: 343-8391

Email: ParkerRW@muni.org

Project: Alaska Regional

Review Number: 291127

 

1) STATUS:  4-11-12 Comments to be addressed.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 

3) M1.2         The LP Boiler has now been isolated from the main hot water system by the heat exchanger. Provide a new expansion tank for this boiler. (IMC 1009)

 

4) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.

 

 

 