Reviewed by: Bergstrom, Leigh Permit #: M12-1212
Phone: 343-8326 Date: 4/11/2012
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: ParkerRW@muni.org
Project: Alaska Regional
Review Number: 291127
1) STATUS: 4-11-12 Comments to be addressed.
2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.
3) M1.2 The LP Boiler has now been isolated from the main hot water system by the heat exchanger. Provide a new expansion tank for this boiler. (IMC 1009)
4) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.