Permit Number: X12-1246
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: complete changes to building and outside civil
Status: Closed
Project Name: Change Order of Bldg App C11-1609
Review Type: Structural
Result: Correction
Result Date: 4/10/2012 4:24:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT INFORMATION

Permit Number: C11-1609

Change Order Number: X12-1246

Project Name: Olive Garden Dimond Center

Permit Manager: Tony Barganier | ph: (907) 343-8339 | barganierta@muni.org

 

Plan Review: Mark Panilo | ph: (907) 343-8081  fax: (907) 249-7679 | panilomm@muni.org

 

Please submit all information through your Permit Manager.

 

REVIEW STATUS

04/10/2012 – Initial review (290954).  Comments issued.

 

1. LATERAL RESTRAINT OF ENTRY ROOF

Refer to Sheet S3.2, Detail 17/S4.4.  Please clarify the lateral restraint of the high roof at the entry.  Given the location and orientation (horizontal and vertical) of the HSS 4x4 struts, it seems that there are no ways of developing a tension/compression couple to transfer loads from the upper roof to the main roof for transverse displacements; all of the connections are pinned, and the struts are eccentric to both the horizontal and vertical centers of mass.

Reference: IBC Section 1604.4

 