Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C12-1238
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: TENANT IMPROVEMENT INCLUDES ELEC, PLMB AND MECH (JINNY ROSE DAY)
Status: Closed
Project Name: BILLABONG
Review Type: Architectural
Result: Approved
Result Date: 4/3/2012 10:08:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Architectural Comments

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C12-1238

Phone: 343-8451                                                                        Date: 4/3/2012

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: JINNY Rose Day

Phone: 343-8338

Email: dayjr@muni.org

Project: Billabong (Fax to 349-1325)

Review Number: 290725

______________________________________________________________________________

1.  Status: Full Architectural Approval.  4/3/12

 

1)  The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations. 

 

2)   REQUIREMENT OF ELECTRICAL SCOPE OF WORK:
Please provide the electrical scope of work and include existing service load calculations, panel schedules with connected and demand loads, one-line diagram and accessibility to overcurrent protection so we can determine if work requires 100% designed engineered.    Resolved.  The Engineered Electrical Design was submitted.  4/3/12

 

3)  CODE ANALYSIS:

Sheet A10 (Construction Type). The code study shows the construction type to be V-unrated. Please justify the type of construction.   Resolved.  The code study was redlined to indicate construction type II-N.  4/3/12

 

4)  CODE ANALYSIS:

Sheet A10 (Occupant Load Calculation Table). The code study reference occupant load per table 1003.2.2.2. this is a typo because the correct table which is 1004.1.1 is referenced as header of the paragraph.   Resolved.   The code study was redlined to indicate Table 1004.1.1.  4/3/12

 

5)  CODE ANALYSIS:

Sheet A10 (Egress Doors). The second egress door when fully opened encroaches on the existing hall corridor from opening. Please review and address.   Resolved.  The drawing was clarified to indicate that the existing situation encroaches only 8 or 9 inches (much less than half).  4/3/12

 

6)   When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, engineers stamp and signature. Resolved.  The comments were resolved by Redline. 4/3/12

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter