Permit Number: C12-1218
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description: TENANT IMPROVEMENT TO CONSTRUCT 985 SQ FT OF RETAIL SPACE. WORK INCLUDES NON STRUCTURAL CASEWORK AND FINISHES CONSISTENT WITH TYPICAL T/I SCOPE OF WORK. ELECTRICAL, PLMB AND MECH (JINNY ROSE DAY)
Status: Closed
Project Name: PANDORA
Review Type: Mechanical
Result: Approved
Result Date: 4/5/2012 10:51:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C12-1218

Phone: 343-8326                                                                            Date: 4/05/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: Pandora

Review Number: 290663

 

1) STATUS:  3-01-12 Comments to be addressed.        4-05-12 APPROVED.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.             RESOLVED 4-5-12.

 

3) M1.0        The new full height wall is blocking the existing 24 x 12 mall return air opening (ref. A2.1).                    RESOLVED PER RESUBMITTAL RECEIVED 4-2-12.            

 

4) M1.0        The Back Room is separated from the front of the store by a full height wall (A2.1 & A6.1) with 650 CFM of return air & exhaust and 200 CFM of supply air. Please clarify the return air path to maintain the balance of air pressure. (IMC 403.1)             RESOLVED PER RESUBMITTAL RECEIVED 4-2-12.            

 

5) The tenant separation wall to the west is required to be a rated 1-Hour partition (IBC 402.7.2). The new 24 x 12 return air opening is required to have a fire damper (IBC 716.5.2).               RESOLVED PER RESUBMITTAL RECEIVED 4-2-12.            

 

6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.         RESOLVED      4-5-12. 

    

 

 

 