Permit Number: C12-1218
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description: TENANT IMPROVEMENT TO CONSTRUCT 985 SQ FT OF RETAIL SPACE. WORK INCLUDES NON STRUCTURAL CASEWORK AND FINISHES CONSISTENT WITH TYPICAL T/I SCOPE OF WORK. ELECTRICAL, PLMB AND MECH (JINNY ROSE DAY)
Status: Closed
Project Name: PANDORA
Review Type: Architectural
Result: Approved
Result Date: 4/4/2012 12:45:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C12-1218

Phone: 343-8326                                                                            Date: 4/04/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: Pandora

Review Number: 290662

 

1) STATUS:   3-01-12 Comments to be addressed.           4-04-12 APPROVED.

 

2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.           RESOLVED 4-04-12.

 

3) A0.1         The 5th Avenue Mall is Type "I-A" construction.         RESOLVED PER RESUBMITTAL RECEIVED 4-2-12.

 

4) Specific fastening details for the glass storefront are to be submitted for structural review on a deferred submittal basis and approved prior to installation. RESOLVED 4-4-12.

 

5) A2.1         The existing tenant separation wall should be 1-hour rated (IBC 402.7.2) and is not so designated as per the Wall Legend.             RESOLVED PER RESUBMITTAL RECEIVED 4-2-12.

 

6) A2.1         The existing shaft wall should be rated for at least 1-Hour or 2-Hours if it connects four levels (IBC 708.4). Please clarify.               RESOLVED PER RESUBMITTAL RECEIVED 4-2-12.

 

7) A2.1         The reference to detail #3/A3.1 storefront, should actually be to detail #2/A3.1.           RESOLVED PER RESUBMITTAL RECEIVED 4-2-12.

 

8) A2.1         The direction of plan North is actually West.            RESOLVED PER RESUBMITTAL RECEIVED 4-2-12.

 

9) A2.1         The new full height wall on the actual north wall, is blocking an existing air transfer grille (See M-1.0). Please clarify.            RESOLVED PER RESUBMITTAL RECEIVED 4-2-12.

 

10) A6.1         Wall type A03 requires a top of wall slip joint. Provide details.   RESOLVED PER RESUBMITTAL RECEIVED 4-2-12.

 

11) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.           RESOLVED 4-4-12.

 

 

 