Permit Number: C12-1421
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: Comm T/I for food service; includes elec,plbg,mech; (16) inspections / tb
Status: Closed
Project Name: CINNABON/SUPERDOG
Review Type: Fire
Result: Approved
Result Date: 4/17/2012 1:43:01 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Approved per phone conversation with architect - Will provide a manual reset on gas valve and relocate K class to meet code.  Fire Inspector will field verify at final.  Plans will be updated in response to other reviewers comments.

1.  Relocate the K class fire extinguisher such that it is accessible and away from the hazard and along the the path of egress.

.

2.  Since the area is more of a prep/serving area is not the appropriate occupancy type F1?

.

3.  The electronic solenoid gas valve supplying the cooking appliances is required to be equipped with a manual reset button.  Please note on plans.

.

4.  The walkin cooler, hood suppression system, & adjustments to the existin fire alarm and sprinkler will require separate submitals, reviews, permits.  These all can be deferred.