Approved per phone conversation with architect - Will provide a manual reset on gas valve and relocate K class to meet code. Fire Inspector will field verify at final. Plans will be updated in response to other reviewers comments.
1. Relocate the K class fire extinguisher such that it is accessible and away from the hazard and along the the path of egress.
.
2. Since the area is more of a prep/serving area is not the appropriate occupancy type F1?
3. The electronic solenoid gas valve supplying the cooking appliances is required to be equipped with a manual reset button. Please note on plans.
4. The walkin cooler, hood suppression system, & adjustments to the existin fire alarm and sprinkler will require separate submitals, reviews, permits. These all can be deferred.