Permit Number: C12-1329
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1553 GAMBELL ST Anchorage
Location:
Work Description: RELOCATE MONOPOLE FROM PARCEL TO THE NORTH NEW LOCATION (JINNY ROSE DAY)
Status: Closed
Project Name: VERIZON WIRELESS
Review Type: Fire
Result: Correction
Result Date: 3/26/2012 3:59:24 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1st Review 3/26/2012 - Corrections required.   Relocate existing antenae to new location.  A fire Inspection is required

.

1.  Provide a fire acceess road to within 150 ft of all exterior points of the facility.  It appears that access off gamble exceeds the allowable 150ft hoseline distance as measured around the fence perimeter.  The 12 ft wide driveway is not considered fire access as a minimum 20 ft width is required.

.

2.  Provide required Knox keybox for entry and appropriate address visible from the street fronting the property. 

.

3.  A fire extinguisher is required for this facility.  Show size, type, & location on plans.