Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C12-1325
Permit Type: Commercial Building Permit - None BldgAlter
Address: N 1080 MULDOON RD Anchorage
Location:
Work Description: New Sam's Club Fueling Station & Canopy / tb  **master fill/grade 07-5165; master file C12-1234**
Status: Closed
Project Name: SAM'S CLUB FUELING STATION 6602
Review Type: Electrical
Result: Approved
Result Date: 3/21/2012 4:52:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Electrical Comments

 

Reviewed by: David Abuobaid                                                   Permit #: C12-1325

Phone: 343-8333                                                                        Date: 3/22/2012

Fax:     249-7775

Email:  AbuobaidDH@muni.org

Permit  Manager: Tony Barganier

Phone: 343-8339

Email:  BarganierWA@muni.org

Project: Sams/s Fuel Station (Fax: 214-749-0601)

____________________________________________________________________________________

1. Please address the following comments for approval. 3/22/2012

 

2.  The following comments based on the 2008 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications do not permit the violation of any section of the NEC or any federal, state or local regulations.

 

3.  EQUIPMENT REQUIRES THIRD PARTY LISTING:
Please be aware that all equipment will require and be checked for third party listing per NEC 110-3. Any new or existing equipment to be reused or relocated will be checked for listing by the electrical inspector. Any equipment found without a listing will be required to go through testing to gain approval. Inspector to field verify.

 

4.  DOCUMENTATION (HAZARDOUS LOCATION CLASSIFIED):

Sheet FKE1 (Gas Pumps). Please add to the plans the floor plans for the canopy. Add hazardous classification diagram around the canopy and the gas dispensing units as required by NEC Sections 500.4 and 514.

The documentation has been provided with dimension of classified location. Approved

 

5.   When the above comments have been addressed, please update the electrical plans at the MOA

Plans Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical engineers stamp and signature.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS