Permit Number: C12-1324
Permit Type: Commercial Building Permit - None BldgNew
Address: N 1074 MULDOON RD Anchorage
Location:
Work Description: 146,500 sq ft new comm bldg / tb **master fill/grade 07-5165**
Status: Closed
Project Name: SAMS CLUB 6602
Review Type: Mechanical
Result: Correction
Result Date: 4/2/2012 3:09:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C12-1324

Phone: 343-8326                                                                          Date: 4/2/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Sam's Club 6602

Review Number: 289810

 

1) STATUS:  4-2-12 Comments to be addressed.

 

2) The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 

3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for RTU-1 thru 24, AHU-1, EH-1& 2 and the Compressor House to include engineers stamp and signature, for structural review on a deferred submittal basis.

 

4) M1, M2 & GM1          "Non-metallic ducts (fabric duct) shall be constructed with Class 0 or Class 1 duct material in accordance with UL 181." (IMC 603.5) Provide submittal literature supporting the requirements.

 

5) 3/M2          Clarify the makeup air path into the janitors closet.

 

6) GM1          The Fire Pump Room is a required 1-Hour enclosure (with sprinkler) and requires fire dampers on any duct penetrations or air transfer penetrations. (IMC 716.5.2)

 

7) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.

 

 

 

 