Building Safety Division
Fire system comments
Reviewed by: Mark Warren Permit #: f12-1039
Phone: 267-4992 Date: 2/14/2012
Fax: 249-7397
Email: warrenmj@mini.org
Permit Manager: Bob Parker
Phone: 343-8320
Email: parkerw@muni.org
Project: 2925 Debarr
Review Number: 288525
____________________________________________________________________________________
PERMIT STATUS: corrections ; approved on 4/9/2012
1) Provide plans for the penthouse and show the required duct detectors at the required RTU’s and include them in the Matrix.
2) Show minimum required horn strobes at the future T.I. build out areas.
The items above are resolved with the exception that the RTU's are still not shown. 3/22/2012.
The items above were resolved on 4/9/2012.