Permit Number: C12-1227
Permit Type: Commercial Building Permit - None BldgNew
Address: 3550 PROVIDENCE DR Anchorage
Location:
Work Description: 24,842 (A3), 98, 752 (A4), 44,175 (B), 28,991 (S2) (JINNY ROSE DAY)
Status: Closed
Project Name: UAA SPORTS ARENA
Review Type: Plumbing
Result: Correction
Result Date: 4/20/2012 8:14:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C12-1227

Phone: 343-8326                                                                            Date: 2/20/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: UAA SPORTS ARENA

Review Number: 289396

 

1) STATUS:   4-20-12 Comments to be addressed.

 

2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.

 

3) M101 Sheet Note #3          This food service floor drain requires trap seal protection (UPC 1007) and a vented P-trap (UPC 901.1).

 

4) M101              The 2" FCO upstream of fixture K-1 serves a 3" W line 8 feet downstream. This FCO and interconnecting piping are required to be at least the same size as the 3" main downstream. (UPC Table 7-6)

 

5) M101              The 2" FCO adjacent to fixture K-4 serves a 3" W main downstream and a 4" main further downstream. This cleanout is required to be the same size as the largest pipe served. (UPC Table 7-6)

 

6) M102              FD-1 in Laundry B1220 requires trap seal protection (UPC 1007).

 

7) M104              The four FD-1's at the 4 exits from the Performance Gymnasium, one in Janitor B1180 and one in Toilet B1210 require trap seal protection (UPC 1007).

 

8) M106              The floor drains in Ski Storage B1015 and Pump B1017 require trap seal protection. (UPC 1007).

 

9) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.

 

 