Permit Number: C12-1227
Permit Type: Commercial Building Permit - None BldgNew
Address: 3550 PROVIDENCE DR Anchorage
Location:
Work Description: 24,842 (A3), 98, 752 (A4), 44,175 (B), 28,991 (S2) (JINNY ROSE DAY)
Status: Closed
Project Name: UAA SPORTS ARENA
Review Type: Architectural
Result: Correction
Result Date: 4/21/2012 8:15:13 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Crafts, Donald E.                                                  Permit #: C12-1227

Phone: 343-8451                                                                        Date: 4/21/2012

Fax: 249-7652

Email: CraftsDE@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: UAA SPORTS ARENA

Review Number: 289392  

 

1.  Status: Architectural Corrections required.  Status: Footing and Foundation Architectural Approval.  Please resolve comments and provide complete submittal for Shell and Core Construction Architectural review.  4/21/12

 

2.  The following comments based on the 2009 International Building Code (IBC) must be resolved before a permit is issued.  The plans and specifications do not permit the violation of any section of the IBC or any federal, state, or local regulations.

 

3.  Drawing A020, Code Review, Revise: International Building Code (IBC) 2006 Edition, to: International Building Code (IBC) 2009 Edition.  The following codes are applicable to this project: 

International Building Code (IBC) 2009

International Fire Code (IFC) 2009

International Mechanical Code (IMC) 2009

International Fuel Gas Code (IFGC) 2009

International Energy Conservation Code (IECC) 2006

Uniform Plumbing Code (UPC) 2009

National Electric Code (ICC/NEC/NFPA 70) 2008

Accessible and Useable Buildings and Facilities (ICC/ANSI A117.1) 2003

 

4/19/12

 

4.  Drawing A020, Code Review, Balcony Walkway Mezzanine, Revise: 3,870 SF OK Since <50%, to: 3,870 SF OK Since <50% per 505.2, exception 2.  The requirements of this exception include Sprinklers (which is already noted in the code study in accordance with 903.3.1.1) and Emergency Voice/Alarm Communication System (which needs to be noted in the code study in accordance with 907.5.2.2).  4/19/12

 

5.  Drawing A020, Code Review, Heavy Timber, Revise: 603.1, exception 16, to: 603.1, exception 18.  4/19/12

 

6.  Drawing A020, Code Review, Incidental Use, Revise: 508.2, to: 508.2.5.  4/19/12

 

7.  Drawing A020, Code Review, Shaft Enclosures, Revise: 707.4, to: 708.4.  4/19/12

 

8.  Drawing A020, Code Review, Shaft Enclosures (Elevator), Revise: 707.14, to: 708.14.  4/19/12

 

9.  Drawing A020, Code Review, Vertical Exit Enclosures, Revise: 1020.1, to: 1022.1.  4/19/12

 

10.  Drawing A020, Code Review, Dead End Corridor, Revise: 1017.3, to: 1018.4.  4/19/12

 

11.  Drawing A020, Code Review, Travel Distance Requirements, With Sprinkler (Table 1016.1), Revise: 300 Ft Max, to: 300 Ft Max (Except 250 Ft Max for A-3 and A-4 areas).  4/19/12

 

12.  Drawing A020, Code Review, Travel Distance Requirements, Common path of Travel (with sprinklers), Revise: 100 Ft Max, to: 1014.3, exception 1, 100 Ft Max (Except 75 Ft Max for A-3 and A-4 areas).  4/19/12

 

13.  Drawing A(all), All Architectural Sheets, The submitted architectural plans and code study are not sealed and signed by an Alaska licensed architect.  Please provide an architectural plans and code study sealed and signed by an Alaska licensed architect.  4/19/12

 

14.  Drawing A020, .  4/19/12