Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X11-1752
Permit Type: Commercial Building Permit - ChangeOrdr BldgNew
Address: 4140 B ST Anchorage
Location:
Work Description: Glazed curtain wall shop drawings / tb
Status: Closed
Project Name: Change Order of Bldg App C11-1407
Review Type: Structural
Result: Approved
Result Date: 3/2/2012 12:49:32 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT INFORMATION

Permit Number: C11-1407

Change Order Number: X11-1752

Project Name: B Street North

Permit Manager: Jinny Rose Day | ph: (907) 343-8338 | dayjr@muni.org

 

Plan Review: Mark Panilo | ph: (907) 343-8081  fax: (907) 249-7679 | panilomm@muni.org

 

Please submit all information through your Permit Manager.

 

REVIEW STATUS

10/26/2011 – Initial review (284529).  Comments issued.

 

1. REVIEW FOR GENERAL CONFORMANCE

Please provide indication that the registered design professional has reviewed this deferred submittal for general conformance with the design drawings.

Reference: AMC 23.10.104.9

 

2. DESIGN CALCULATIONS / LOAD TABLES

No design calculations or load tables were provided with the shop drawings.  Please provide.

Reference: IBC Section 1604.4

 

3. SECTION PROPERTIES/TYPES

The plans are not clear as to the section properties or types for the various components.  All that is given is a part number.  Please clarify and coordinate with Comment 2 above.

Reference: IBC Section 1603.1; AMC 23.10.104.8.1

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS