REVIEW STATUS
10/26/2011 – Initial review (284529). Comments issued.
1. REVIEW FOR GENERAL CONFORMANCE
Please provide indication that the registered design professional has reviewed this deferred submittal for general conformance with the design drawings.
Reference: AMC 23.10.104.9
2. DESIGN CALCULATIONS / LOAD TABLES
No design calculations or load tables were provided with the shop drawings. Please provide.
Reference: IBC Section 1604.4
3. SECTION PROPERTIES/TYPES
The plans are not clear as to the section properties or types for the various components. All that is given is a part number. Please clarify and coordinate with Comment 2 above.
Reference: IBC Section 1603.1; AMC 23.10.104.8.1