1st Review 2/21/2012 - Corrections required. Provide a written response to each comment along with revised plans.
.
1. Correct code study as it references the 2006 IBC, IRC, etc. The codes in effect are the 2009 editions. Also this is not a residential building.
Resolved 2/22/2012 under "Revision 5" new sheet A00-10 in response to original architectural comments.
2. Provide fire extingishers (FE's) as required per IFC 906. Show size, type, & location on plans for the entire floor whether existing or new. Travel distance from any point on the floor shall not exceed 75 ft to an FE. On what plan sheets are the FE's or FEC's shown?
3. Show location of all required emergency light fixtures for the entire floor whether existng or new.
4. The existing double sided exit sign outside the cafe may be confusing and not necessary. The exit sign leading thru the reception lobby should be avove the door and not necessarily depict a directional arrow. Door 0619B, although not in the work area appears as if it also should have an exit sign. The new exit signs within and outside the training room seem unneccesary and confusing. The existing exit sign @ W3/F should not depict directional arrows.
5. Every occupant of the floor shall have access to two independent exits at all times. Will the doors serving access to the 2nd required exit from Elevator Lobby 0600 & Reception Area 0602 be unlocked at all times? Tenants may not exit thru other tenant spaces. It appears that exiting to a 2nd stair from cafe 0623 is required to exit thru door 0619A which locks against egress as it requires a card reader.
6. Door 0630A appears to be an access controlled exit device. Per IBC 1008.1.4.4 these devices are only allowed on entrance doors to tenant spaces. The size of the room makes this device impractical as any movement within the room will constantlt release the lock. A more appropriate set up may be to provide hardware in compliance with IBC 1008.1.9.8. Please comment.