Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C12-1162
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 701 8TH AVE Anchorage
Location:
Work Description: ISOLATED WALL RELOCATION, PAINT, FLOORING, HVAC, ELECTRICAL, TYPICAL TENANT IMPROVEMENT (JINNY ROSE DAY)
Status: Closed
Project Name: KPMG
Review Type: Architectural
Result: Correction
Result Date: 2/14/2012 2:10:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C12-1162

Phone: 343-8326                                                                           Date: 2/14/2012

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: KPMG

Review Number: 288272

 

1) STATUS:   2-14-12 Comments to be addressed.

 

2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.

 

3) A00-10 Code Analysis          With the exception on the NEC, the Municipality of Anchorage has adopted and is reviewing under the 2009 codes.

 

4) A00-50 & A04-06        Please clarify the lock on door #0619A. There should be panic hardware on the push side to gain access to the exit and if the lock is on the pull side personnel using the bathrooms would not be able to get back to their work stations.

 

5) A04-06           Please clarify the reference to Closet #0617 in Hallway #0616.

 

6) A04-06           The page reference for details D4 & D5 in Cafe 0623 should be to A10-02.

 

7) C2, C5 & D4/A10-02           The 2'-10" elevation should specifically be to the flood rim of the sink (ICC/ANSI A117.1-606.3. Please clarify.

 

8) 12 & 13/A10-51          Provide a listed top of wall detail for these rated wall assemblies.

 

9) Two copies of sheets A02-06, A05-06 & A06-06 were provided but with different revision dates. Please remove the older revisions.

 

10) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.

    

 

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS