Reviewed by: Bolen, Wayne A. Permit #: C12-1042
Phone: 343-8072 Date: 1/19/2012
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: New RBS at 601 W 5th Ave
Review Number: 287467
____________________________________________________________________________________
PERMIT STATUS
1/19/2012 – Permit reviewed. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1) Please indicate the clamp type, and show that the clamp has enough mechanical friction capacity to transfer the load to the platform. Friction generated from the weight of the unit is not permitted to resist lateral seismic forces. Please verify the grating attachment to the platform framing has a positive connection for lateral seismic forces as well as the platform framing to the structure. If the loads to the grating and the platform are not increase by more than 10% no verification of the existing connections is required. Reference ASCE 7-05 section 13.4 and IEBC section 303.3.