Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C11-2021
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3101 PENLAND PKWY Anchorage
Location:
Work Description: SAFEWAY PHARMACY TI TO EXPAND EXISTING WAITING AREA, ADD AN ADA RESTROOM AND ADD A CONSULTATION ROOM. (JINNY ROSE DAY)
Status: Closed
Project Name: SAFEWAY #0520
Review Type: Architectural
Result: Approved
Result Date: 11/22/2011 8:33:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C11-2021

Phone: 343-8326                                                                           Date: 11/22/2011

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Jinny Day

Phone: 343-8338

Email: DayJR@muni.org

Project: Safeway #520

Review Number: 285979

 

1) STATUS:   10-19-11 Comments to be addressed.              11-22-11 APPROVED.

 

2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.           RESOLVED 11-22-11.

 

3) A2a                   Plumbing and mechanical plans signed and sealed by an Alaska registered professional mechanical engineer will also be required.     RESOLVED 11-22-11.

 

4) A2a                   Structural plans will be required for the new exterior stairs, the new exterior door and bracing for the overhead roll down fire doors.       RESOLVED 11-22-11.

 

5) A2a                   Handrails are required on both sides of the new exterior stairs (IBC 1009.12)          RESOLVED PER RESUBMITTAL RECEIVED 11-16-11.

 

6) A2a                   Wall types W-2 and W-4 require slip joints at top of wall. Please clarify.          RESOLVED PER RESUBMITTAL RECEIVED 11-16-11.

 

7) A2a                   Where is the location of wall type W-3?           RESOLVED PER RESUBMITTAL RECEIVED 11-16-11.

 

8) 6/A4                  The new concrete wall at the landing and stairs is required to be at least 42" to create a guard (IBC 1013.1).               RESOLVED PER RESUBMITTAL RECEIVED 11-16-11.

 

9) 12/A6               The consulting room sink has ADA requirements to be 34" maximum above the finished floor to the flood rim of the sink or countertop, whichever is higher. (ICC/ANSI A117.1-606.3)          RESOLVED PER RESUBMITTAL RECEIVED 11-16-11. 

 

10) 3D/A4                The required water closet clear space is 60 inches minimum, measured perpendicular from the sidewall with no other fixtures or obstructions within that space (ICC/ANSI A117.1-604.3.1). Please clarify for the benefit of the installing contractor.          RESOLVED PER RESUBMITTAL RECEIVED 11-16-11.

 

11) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, engineers stamp and signature.                       RESOLVED 11-22-11.

 

 

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS