PERMIT INFORMATION
Permit Number: C11-2182
Project Name: ANC Nationwide New Technology Deployment
Permit Manager: Jinny Rose Day | ph: (907) 343-8338 | dayjr@muni.org
Plan Review: Mark Panilo | ph: (907) 343-8081 fax: (907) 249-7679 | panilomm@muni.org
Please submit all information through your Permit Manager.
REVIEW STATUS
11/08/2011 – Initial review (285579). Comments issued.
GENERAL
This review is code compliance review based on the requirements of the International Existing Building Code (IEBC), 2006 Edition, and all adopted references thereto, as amended by the Municipality of Anchorage in Anchorage Municipal Code (AMC) Title 23. This review does not permit the violation of the building codes, nor any federal, state, or municipal regulation.
The following comments must be addressed before a permit may be issued. Additional comments may be issued following review of submitted information.
1. FREQUENCY OF INSPECTIONSPlease note in the Statement of Special Inspections the required frequency of inspections (continuous vs. periodic).
Reference: IBC Section 1705.2
2. SPECIAL INSPECTION PERSONNEL
Please provide a letter from the Owner/Owner's Representative, or Special Inspection Agency stating that the Special Inspection Agency has been retained by the Owner to provide special inspection services for the project as required by IBC Chapter 17.
Reference: AMC 23.15.1704.1.4
3. DESIGN ANALYSIS AND DETAILS
Please provide analysis showing demands on the support system and design calculations showing the adequacy of the proposed bracing and connections.
Reference: IBC Section 1604.4; ASCE 7 Section 13.1.1