Electrical Comments
Reviewed by: David Abuobaid Permit #: 10 5130 (CO. X11-1804)
Phone: 343-8333 Date: 11/10/2011
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: JINNY Rose Day
Phone: 343-8338
Email: dayjr@muni.org
Project: Anchorage Neighborhood Clinic
____________________________________________________________________________________
1-26-2011
The revision has been reviewed and approved.
1. Please address the following comments for approval. 11/10/2011
2. The following comments based on the 2008 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the NEC or any federal, state or local regulations.
3. GROUND FAULT PROTECTION (GFP) REQUIREMENT:
Sheet E3.4 (Ground Fault Protection). The generator and the MDP rating has increased to 1200 A, 480 V. This requires GFP. Please revise the plans to reflect the GFP on the system. Refer to NEC Section 310.95.
4. TYPE OF CONDUCTORS:Sheet E3.4 (Conductor Type. We could not verify if conductors are copper or aluminum. Please state on the plans type of conductors. Refer to NEC Table 310.16. Please
5. NEW REVISED AND ADDED LOAD:
Sheets SKM-1 and E3.4. The changes in this revision include cooling unit, UPS, and other equipment. Please provide the new panel schedule, new loads, and deleted loads. Refer to Anchorage Administrative Code AAC 10.104.8.1.
6. When the above comments have been addressed, please update the electrical plans at the MOA Plans Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical engineers stamp and signature.